ERRCS and Public Safety DAS

Ensuring Reliable In-Building Emergency Communications with ERRCS and Public Safety DAS Systems

Emergency Responder Radio Communication System (ERRCS) and Public Safety Distributed Antenna Systems (DAS) play a critical role in strengthening in-building radio coverage for first responders, especially in large or complex structures where signals may be weak. Proper installation, inspection, and maintenance of these systems are essential to ensuring compliance with fire codes and FCC regulations, as well as maintaining public safety.

Below, you'll find key requirements for system testing, inspection, and reporting, along with a link to local service providers who specialize in ERRCS/DAS installation and maintenance.

Inspection and Testing Requirements for Commissioning, Annual Testing, and Repairs

Below is an overview. Refer to the ERRCS/ DAS application packet for complete information. 

  1. All inspection and testing shall comply with the International Fire Code currently adopted by the jurisdictional fire code official.
  2. All final test reports shall be submitted to CRESA within 14 days of the test date. Tests should be submitted electronically in .pdf format to the CRESA Help Desk at helpdesk@cresa.wa.gov.
  3. Place or update a dated and signed standardized label on the amplifier that is easy to read allowing the Fire Official to confirm the device meets FCC, local, and state requirements and has been inspected, calibrated and/or repaired.
  4. Should the equipment be found non-compliant notification shall be made in writing to the Building Owner, Fire Official and CRESA with recommended corrective actions that are required to bring the amplifier/system into compliance and estimated time of repair.
  5. Maintain a database of locations, equipment specifics, and inspection/calibration/repair information for each system and provide a list of locations to CRESA as may be requested.

Local service providers for BDA/DAS systems:

Jim Muzynoski 

Owner/Director of Operations 
Amplified Wireless Solutions, Inc. 
(503) 686-0670, cell 
jmuzynoski@a-w-s-inc.com 

Janis A. Christensen 

Operations & Logistics Manager 
Clearline Engineering 
(206) 512-4030 
jchristensen@clearlineengineering.com 

John Marchette 

Performance System Integration 
(503) 641-2222 
JohnM@psintegrated.com 

Eric J. Willard 

Project Manager 
Azimuth Communications 
(503) 563-5978 x132, office 
(503) 341-2967, cell 
eric@azimuthcommunications.com 

Scott Tulp 

Wireless Systems Sales Representative 
Day Wireless Systems 
(503) 519-3239, cell 
(360) 256-9444, office 
STulp@daywireless.com 

Documents

Explore more